Abu Dhabi Fire Code Amendments 2026: What ADCDA Circular No. 3 Changes for Your Project
/// OUR INSIGHTS

Abu Dhabi Fire Code Amendments 2026: What ADCDA Circular No. 3 Changes for Your Project

Explore the 54 amendments introduced by ADCDA Circular No. 3 – 2026 and their impact on building classification, fire protection systems, industrial facilities and fire and life safety design in Abu Dhabi.

Home→Insights→Abu Dhabi Fire Code Amendments 2026: What ADCDA Circular No. 3 Changes for Your Project
←Article
Abu Dhabi Fire Code Amendments 2026: What ADCDA Circular No. 3 Changes for Your Project
Nov 24, 2026
Xeluxe Team
15 Min Read

Explore the 54 amendments introduced by ADCDA Circular No. 3 – 2026 and their impact on building classification, fire protection systems, industrial facilities and fire and life safety design in Abu Dhabi.

On 12 March 2026, the Abu Dhabi Civil Defence Authority (ADCDA) issued Circular No. 3 – 2026. It contains 54 decisions that amend the UAE Fire and Life Safety Code of Practice (2018 edition) for projects in Abu Dhabi.

Many of these decisions are not new ideas. They formalise relaxations that Civil Defence had been granting case by case, and most of them bring the Code closer to NFPA. For design teams that is welcome: fewer special-case justifications and more predictable approvals.

But a few of the changes do more than relax a detail. They can change which requirements apply to a building in the first place. This guide covers the changes that matter most for design, what they mean for warehouses and industrial projects, and a summary of every other decision in the circular.

For background on the Code itself, see our practical guide to the UAE Fire and Life Safety Code of Practice.

Key takeaways

  • Circular No. 3 – 2026 makes 54 amendments to the 2018 UAE Fire and Life Safety Code. It applies in Abu Dhabi only, and the Arabic text is the governing version.
  • The change with the widest effect is building height: it is now measured to the finished floor level of the highest occupied storey, not to the top of the roof wall.
  • Several system requirements are removed or relaxed, including balcony sprinklers, clean agent in panel-only electrical rooms, and private hydrants where public hydrants are within 100 m.
  • Warehouses and industrial buildings gain the most relaxations, from roof-level separation to in-rack sprinkler clearances and voice evacuation.
  • The English translation does not state an effective date or transition rules for projects already under review, so confirm these with ADCDA for live submissions.

What is ADCDA Circular No. 3 – 2026?

ADCDA Circular No. 3 – 2026 is a set of 54 decisions issued by the Abu Dhabi Civil Defence Authority on 12 March 2026. It amends selected provisions of the UAE Fire and Life Safety Code of Practice (2018) for projects in the Emirate of Abu Dhabi, largely aligning them with NFPA. It does not replace the Code, and it does not apply in other emirates.

The 10 changes most likely to affect your design

1. Building height is now measured to the highest occupied floor (Decision 11)

What changed: For classifying buildings and their fire protection systems, height is now measured to the finished floor level of the highest occupied storey, following NFPA 101. The 2018 Code measured to the top of the roof wall.

What to check: This is the change to look at first. Height drives classification, and classification drives most system requirements. A tower close to a threshold, such as the 90 m super high-rise limit, may now fall into a lower category once roof plant, parapets and an unoccupied roof are excluded. Re-run the classification on every project near a threshold before assuming the 2018 requirements still apply.

2. Balcony sprinklers are no longer required (Decision 09)

What changed: The balcony sprinkler requirement in Chapter 9, Table 9.29 (Item B) is cancelled.

What to check: Removing sprinklers from balconies does not remove the risk of fire spreading up a façade from a balcony. Façade material, balcony finishes and stored items still matter, and the Code's façade requirements continue to apply. Developers will see a cost saving, but the façade strategy should be reviewed with the sprinklers gone.

3. No clean agent for panel-only electrical rooms (Decision 07)

What changed: Clean-agent suppression is no longer required in main electrical or telephone rooms that contain only panels or control units, whatever their size, provided all wall penetrations are fire-stopped. Previously, rooms over 10 m², including those on typical floors, needed it.

What to check: The waiver depends on the room containing only panels or control units. Rooms with transformers, batteries or UPS equipment are a different case. Fire stopping becomes the condition of approval, so it needs to be specified clearly and inspected.

4. Private hydrants can be replaced by public hydrants (Decisions 08 and 14)

What changed: For industrial and warehouse occupancies with a ground floor over 3,600 m², the private hydrant network can be exempted if public external hydrants are within 100 m of the facility (Decision 08). Decision 14 extends this principle: where public hydrants are available, they may replace private hydrants required for buildings or industrial occupancies.

What to check: Confirm that the public hydrants can actually deliver the flow and pressure your fire strategy relies on, and how the 100 m is measured. Fire service access to those hydrants also matters. For high-hazard storage, sizeable on-site water may still be the safer design choice.

5. Warehouse separation no longer extends above the roof (Decision 01)

What changed: The 2018 requirement for full-height separation between warehouses to extend 760 mm above roof level is cancelled.

What to check: Multi-unit sheds gain simpler roof detailing. With no upstand, though, the roof itself becomes the route for fire spread between units, so check roof construction, insulation and any rooftop solar panels across the separation line.

6. Relaxed compartmentation in sprinklered buildings (Decisions 04 and 05)

What changed: Smoke barriers and partitions no longer need a 1-hour fire rating where the building is sprinklered (clause 1.1.17). On typical floors, service rooms still need 1-hour isolation from escape corridors, but their doors no longer need to be fire-rated provided all wall penetrations are fire-stopped.

What to check: These save door and partition costs on every floor of a tower, but they rely on two things: the building being fully sprinklered, and fire stopping being done properly. Both should be clearly specified in the fire strategy.

7. One-hour exit stairs in new buildings up to three storeys (Decision 42)

What changed: Exit stair enclosures in new buildings of up to three storeys need 1-hour fire resistance instead of 2 hours, applying NFPA 101 clause 7.1.3.2.1.

8. Larger occupant load factor for offices (Decision 43)

What changed: Non-crowded general offices can use an occupant load factor of 14 m² per person instead of 9.3, in line with NFPA Table 7.3.1.2.

What to check: This lowers the calculated occupant load by about a third, which can reduce exit widths and stair numbers on large floor plates. It is for general office use only, not crowded business areas.

9. Relaxations for buildings over 90 m (Decisions 06, 38 and 54)

What changed: The telephone jack system is now required only in super high-rise buildings above 90 m. Buildings up to 100 m no longer need an intermediate fire pump, and one pump is acceptable if hydraulic calculations show adequate flow and pressure at the top floor. Elevators inside apartments in buildings over 90 m no longer need lobbies and pressurisation; approved fire curtains linked to the fire alarm can be used instead.

10. Three categories of duct fire insulation (Decision 53)

What changed: HVAC duct fire insulation is now set by case: Case A keeps 2-hour insulation, Case B allows 1 hour, and Case C needs none. ADCDA has also issued a separate technical circular on smoke management ducts that uses the same three-category approach, with kitchen exhaust and pressurisation ducts always kept in the highest category.

What to check: Which category applies depends on where the duct runs and what it serves. Duct routes through exit stairs, refuges or firefighting access should be assumed to stay at full protection until confirmed.

What the amendments mean for warehouses and industrial projects

Industrial and logistics buildings gain more from this circular than any other building type. Beyond the roof separation and hydrant changes above:

  • In-rack sprinkler warehouses (Decision 48): The spacing between racks and non-bearing walls can be removed, and aisle and clearance provisions are not required, applying NFPA. This applies to low and medium hazard storage only.
  • Voice evacuation (Decision 47): Factories and warehouses over 5,000 m² can use bells and flashers instead of voice evacuation, with an official letter confirming staff are trained in evacuation.
  • Ventilation (Decisions 25 and 26): Industrial buildings under 900 m² are exempt from ventilation requirements, and existing industrial facilities are exempt from ventilation and façade requirements unless hazardous materials are present.
  • Construction type (Decision 23): NFPA 5000 is used for Type II (000) industrial construction, which the 2018 Code did not clarify.
  • Specialist detectors (Decision 39): Limited-use detectors such as multi-gas, ammonia, hydrogen and explosion-proof types can be approved with a certified report, even if not listed, which helps cold stores, battery rooms and process areas.

Taken together, these make large sheds simpler and cheaper to approve. The hazard has not changed, though. Storage commodity, rack height and the presence of dangerous goods should still drive the fire strategy, especially where a relaxation is limited to low and medium hazard storage.

All other amendments at a glance

Existing buildings and extensions

  • Decision 12: Where 2018 provisions cannot be applied to an existing building, NFPA or other international references may be used.
  • Decision 13: Vertical extensions need sprinklers on the new floors only.
  • Decision 16: Existing buildings with no prior Civil Defence approval, where NFPA cannot be applied, go to a special committee with a risk assessment covering response time and evacuation.

Specific occupancies and small buildings

  • Decision 18: Villas converted to commercial use need an external stair only for nurseries or where any floor exceeds 500 m², and only basic systems (alarm, extinguishers, emergency lighting, exit signs).
  • Decision 19: Farm projects are exempt from firefighting systems unless non-residential buildings exceed 500 m².
  • Decision 20: Schools under 15 m are exempt from corridor mechanical ventilation and stair pressurisation.
  • Decision 22: Nurseries in villas have relaxed lease, classroom-floor and corridor fire door rules where smoke doors are provided.
  • Decision 31: Mosques need only extinguishers, emergency lighting and exit signs in the prayer hall, with alarm and extinguishers for the Imam residence.
  • Decision 33: Small low-rise mercantile, assembly, education and healthcare buildings under 500 m² need only extinguishers and a fire alarm.
  • Decision 34: Mercantile occupancies need sprinklers only above 1,115 m², per NFPA.
  • Decision 36: Low-rise apartment buildings under 500 m² with no basement and up to two apartments per floor are exempt from hose systems.
  • Decision 37: Shops over 3,600 m² are no longer automatically treated as malls.
  • Decision 40: Civil Defence centres are exempt from suppression systems where there is no other use.
  • Decision 44: Outpatient clinics are classified as business occupancy rather than healthcare.
  • Decision 46: Fire doors are no longer required in converted villas used for commercial occupancies.

Fire protection systems and products

  • Decision 10: Updated test standards are reviewed within 6–12 months and then become mandatory; high-risk products must test to the new standard immediately.
  • Decision 17: Laboratory testing can be waived for fire pumps below 250 GPM, subject to NFPA 20 compliance, factory testing and a minimum 5-year warranty.
  • Decision 21: Landing valves can be in corridors or stairs, at the designer's choice.
  • Decision 29: Listed mobile fire pump units accepted by Civil Defence are permitted.
  • Decision 35: Small GRP substations of 15 m² or less with no occupancy need only extinguishers.

Building elements and services

  • Decision 02: Where fire-rated architectural projections are not provided, testing of the floor-separating fire barriers is recommended (guidance, not mandatory).
  • Decision 03: Separation of Group 1 assembly occupancies applies only where an assembly area exceeds both 50 occupants and 100 m².
  • Decision 24: Waste rooms may be on the ground floor or first basement, with sprinklers, a self-closing fire-rated door and an owner's undertaking.
  • Decisions 28 and 32: Fire pump rooms at ground level, and small control and generator rooms, can rely on natural ventilation.
  • Decision 30: HVAC units are permitted in exit stairs with a fire-rated enclosure, smoke dampers, alarm connection and a maintenance commitment.
  • Decision 41: Mezzanines in new buildings can be up to 50% of the room area, applying NFPA.
  • Decision 45: Corridors in non-sprinklered business and mercantile buildings need not be fire-rated, per NFPA.
  • Decision 52: Inflatable domes can be approved as Class B construction.

Site, infrastructure and solar

  • Decision 15: Civil Defence vehicle access reverts to the 2011 Code (T-turn, 19 m turning width, 4 m road width).
  • Decision 27: External 11/22 kV substations in residential areas need only portable extinguishers.
  • Decision 49: Vehicle tunnels follow NFPA 502 for ventilation, suppression and fire alarm.
  • Decisions 50 and 51: Rooftop solar needs an adequate roof exit per NFPA 1 (except villas); open-area solar such as car park canopies needs only product approval.

How to apply the amendments on a live project

  1. Get the official Arabic circular from ADCDA. Use the English translation for reference only.
  2. Re-check building height and classification under Decision 11 first, because it can change everything that follows.
  3. List the decisions that apply to your building type and note the 2018 clause each one modifies.
  4. Check the conditions attached to each relaxation, such as full sprinkler protection, fire stopping or hazard class, and make sure they are written into the fire strategy and specifications.
  5. For projects already submitted, confirm with ADCDA whether the amendments can be applied at the current review stage.
  6. Record which decisions you have relied on in the fire strategy report, so reviewers and future owners can trace the basis of the design.

Frequently asked questions

What is ADCDA Circular No. 3 – 2026?

It is a circular issued by the Abu Dhabi Civil Defence Authority on 12 March 2026 containing 54 decisions that amend the UAE Fire and Life Safety Code of Practice (2018) for projects in Abu Dhabi. Most decisions align the Code more closely with NFPA.

How many amendments are in the 2026 Abu Dhabi fire code circular?

There are 54 decisions. They cover building classification, compartmentation, sprinklers, hydrants, fire pumps, ventilation, alarms, existing buildings and specific occupancies such as warehouses, mosques, schools and converted villas.

How is building height measured under the 2026 amendments?

For system classification, height is measured to the finished floor level of the highest occupied storey, following NFPA 101. The 2018 Code measured to the top of the roof wall, so some buildings may now fall into a lower height category.

Are balcony sprinklers still required in Abu Dhabi?

No. Decision 09 cancels the balcony sprinkler requirement in Table 9.29 of the 2018 Code. Façade fire safety requirements still apply, so the façade strategy should be reviewed when sprinklers are removed.

Is a private hydrant system still required for industrial buildings?

Not always. Industrial and warehouse buildings with a ground floor over 3,600 m² can be exempted if public hydrants are within 100 m, and public hydrants may replace private ones more generally where available.

Do the amendments apply in Dubai or other emirates?

No. The circular is issued by ADCDA and applies in Abu Dhabi only. Dubai and the other emirates follow their own Civil Defence requirements.

Do the amendments apply to projects already under review?

The English translation does not state an effective date or transition rules. Confirm with ADCDA how they apply to submissions already in progress.

Final thoughts

Circular No. 3 – 2026 is one of the most practical updates to the Code since 2018. It removes many of the requirements that design teams used to negotiate project by project, and it gives clearer, NFPA-based answers. The risk is treating every relaxation as automatic. Nearly all of them carry a condition, and the height change can quietly move a building into a different category.

XELUXE prepares fire strategies and Civil Defence submissions in Abu Dhabi under ADCDA House of Expertise accreditation. If you are checking how these amendments affect a project, our Fire and Life Safety services team is happy to talk it through, or you can get in touch.

Disclaimer: This article summarises ADCDA Circular No. 3 – 2026 based on an unofficial English translation. The Arabic text governs. Always confirm requirements against the official circular before relying on them for design or compliance decisions.